Ford Escape: Climate Control System - General Information / General Procedures - Evaporator Core Leak Check
			
			Inspection
 
 
 - 
 Recover the refrigerant. 
 Refer to: Air Conditioning (A/C) System Recovery, Evacuation and 
Charging (412-00 Climate Control System - General Information, General 
Procedures).
 
 - 
 Disconnect the evaporator from the A/C system. Refer to the appropriate
 removal and installation section in Group 412 for the procedure.
 
 - 
 Use the correct adapters with the A/C Service Unit to test the 
evaporator. The adapters are part of the A/C flushing kits. For the 
correct adapters and A/C Service Unit,
 Refer to: Climate Control Tools and Equipment (412-00 Climate Control System - General Information, General Procedures).
 
 - 
 NOTE: 
 The automatic shut-off valves on some hoses do not 
open when connected to the fittings. If available, use hoses without 
shut-off valves. If hoses with shut-off valves are used, make sure the 
valve opens when attached to the adapter fittings. The test is not valid
 if the shut-off valve does not open.
  Connect the hoses from the A/C Service Unit to the adapter fittings on the evaporator.
 
 - 
 Open both valves and start the vacuum. Allow the A/C
 Service Unit to vacuum for a minimum of 45 minutes after the low 
pressure gauge indicates 101 kPa (30 in-Hg). The 45-minute evacuation is
 necessary to remove any refrigerant from oil left in the evaporator. If
 the refrigerant is not completely removed from the oil, outgassing will
 degrade the vacuum and appear as a refrigerant leak.
 
 - 
 If the low pressure gauge reading will not drop to 101 kPa (30 in-Hg) when the valves are open and the A/C
 Service Unit is operating, close the valves and observe the low 
pressure reading. If the pressure rises rapidly to zero, a large leak is
 indicated. Recheck the adapter fitting connections before installing a 
new evaporator.
 
 - 
 After evacuating for 45 minutes, close the valves and 
stop the service unit. Observe the low pressure gauge; it should remain 
at the 101 kPa (30 in-Hg) mark.
 
 - 
 If the low pressure gauge reading rises 34 or more 
kPa (10 or more in-Hg) of vacuum from the 101 kPa (30 in-Hg) position in
 10 minutes, a leak is indicated.
 
 
 - 
 If a very small leak is suspected, wait 30 minutes and observe the vacuum gauge.
 
 
 - 
 If a small amount of vacuum is lost, operate the 
service unit with the valves open for an additional 30 minutes to remove
 any remaining refrigerant from the oil in the evaporator. Then recheck 
for loss of vacuum.
 
 
 - 
 If a very small leak is suspected, allow the system 
to sit overnight with vacuum applied and check for vacuum loss.
 
 
 - 
 If the evaporator leaks, as verified by the above 
procedure, install a new evaporator. Refer to the appropriate removal 
and installation Evaporator procedure in Group 412.
 
   Inspection
 
 
 
 NOTE: 
 Depending on refrigerant used:
 
 
 Use a Rotunda-approved Electronic Leak Detector for R134a refrigerant SAE Certified to J2791...
   
 
   Leak detection
 
 
 
 
 Review next note for important refrigerant system dye information.
 
 
 
 NOTE: 
 Fluorescent refrigerant system dye is added to the 
refrigerant system at the factory to assist in refrigerant system leak 
diagnosis using a Rotunda-approved UV 
lamp...
   
 
   Other information:
   What Are Autowipers
Autowipers turns on and controls the 
speed and frequency of the windshield 
wipers.
Autowipers Settings
	Press Settings on the touchscreen.
	Press Vehicle Settings.
	Press Wipers.
	Switch Rain Sensing on or off.
Note: When you switch the feature off, the 
wipers do not operate based on the rain 
sensor...
   
   Activation
 
 
 
 NOTE: 
 Use Refrigerant Identification Equipment to identify
 gas samples taken directly from the refrigeration system or storage 
containers prior to recovering or charging the refrigerant system.
 
 NOTE: 
 Use Refrigerant Identification Equipment that 
conforms to SAE J1771 standard for R-134a or SAE J2912 standard 
identifies R-134a and R-1234yf...